Votre panier
Il n'y a plus d'articles dans votre panier
- Fabricant
- TGE
- Modèle
- Equivalent STAMFORD AS440
TGE-AS440 - Régulation
- +/- 1.0%
- Réglage de la Tension Externe
- +/-10% with 1 k ohm 1 watt trimmer
Increasing resistance lowers voltage - DÉTECTION DE ENTRÉE
- 100-130 Vac 1 phase or
190-264 Vac 1 phase
Frequency 50-60 Hz nominal
Voltage Jumper selectable - OUTPUT
- Current continuous 4A
Resistance 15 ohms min
Voltage 82 V d.c. @ 200 V a.c.
transient 7.5A for 10 secs. - DÉRIVE THERMIQUE
- 0.03% per deg. C change in AVR ambient
- RÉPONSE TYPIQUE DU SYSTÈME
- AVR response 20 ms
Filed current to 90% 80 ms
Machine Volts to 97% 300 ms - SOUS PROTECTION DE FRÉQUENCE
- Set point 94 -98% Hz
- UNIT POWER DISSIPATION
- 12 watts maximum
- ANALOGUE INPUT
- Input resistance 1k ohm
Maximum input +/- 5 Vdc
Sensitivity 1V for 5% Generator Volts - OVER EXCITATION PROTECTION
- Set point 65 V dc
Time delay 10-15 seconds - ENVIRONMENTAL
- 100Hz – 2kHz 3.3g
Operating temperature -40 to +70C
Relative Humidity 0-70C 95%
Storage temperature -55 to +80 °C
Vibration 20-100 Hz 50mm/sec - BUILD UP VOLTAGE
- 4 Volts @ AVR terminals
- POWER INPUT
- Frequency 50-60 Hz nominal
Voltage 100-264 V ac 1 phase - QUADRATURE DROOP INPUT
- 10 ohms burden
Max. input 0.33 A
Max. sensitivity 0.07 A for 5% droop 0PF